Main features:
- Intelligent pre-chamber gas monitoring with 1 tailor-made transducers kit
- Includes 2 high pressure and 1 low pressure transducers
- Compatible with up to 2 manifolds, configurable for up to 60 collectors
- 8 Analog inputs (for pressure transducers)
- 2 digital outputs (for valves, lamps, horns)
- IP68 Classification
- Compatible with Bridgemeter and Bridgemanager at Above-Net for advanced and intelligent operational insights
The Intelligent Gas Data Collection Unit is the ideal kit for any installation that needs real -time consumer, operational and logistics measurements. Available in several different models and kits, allows data to send to the Above-Net Bridgemeter intelligent monitoring solution allowing for the configuration of parameterable alarms and calculations.
Specifications
PDF: Portuguese / English
Technical Specifications
Item | Description |
---|
Enclosure protection | IP68 |
Impact resistance | IK10 |
Flame resistance | UL-94 |
Power supply | 110V - 220VAC |
Energy consumption | Less than 15w |
Communication protocols | Modbus tcp / modbus rti / bridgemeter |
Modbus addresses | 1–247 |
Data format | N, 8.1; and, 8.1; O, 8.1 or N, 8.2 |
Transmission rate | 1200 ~ 115200 BPS |
Analog inputs | 8 standard inputs, ± 150mv, ± 500mv, ± 1V, ± 5V, ± 10V, 0 ~ 150mv, 0 ~ 500mv, 0 ~ 1V, 0 ~ 5v, 0 ~ 10v, 0 20ma, 4 ~ 20ma, ± 20ma |
Digital outputs | 2 exits, open collector up to 30V, maximum load of 100ma |
Installation | Wall assembly |
Operating temperature | 0 ° C A +60 ° C |
Moisture | Relative humidity: 95% (without condensation) |
Net weight | 7 kg |
Remote monitoring | Platform IIOT Bridgemeter |
Dimensions (mm) | A = 311.00; B = 311.00; C = 362.20; F = 127.50; G = 84.00 A '= 298.00; B '= 298.00; C '= 122.70; G '= 79.20; H = 3.30 |
Number of Controlled Manifolds | Up to 2, considering 4 high pressure + 2 line readings (low pressure) + 2 additional inputs (reserves) with option for up to 2 external controls, such as valves, sirens or lamps |